Permit Review Detail
Review Status: Completed
Review Details: TANKS
Permit Number - T11BU01341
Review Name: TANKS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/26/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Provide cut sheets for the tanks, piping, and dispensers indicating the UL or other listing per IFC Section 2206. Detail 5 on Sheet F3.2 must be corrected to show the bollards comply with IFC Section 312 for the four foot spacing or provide a six inch high curb to protect the dispensers. |
| 11/03/2011 | SREEVES1 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/03/2011 | SREEVES1 | ZONING | REVIEW | Needs Review |