Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T11BU01335
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/30/2013 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 02/12/2013 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Approv-Cond | BRC Comments Below are comments for the authorized repair second resubmittal for COT ID# 185 at 803 South 6th Avenue (T11BU01335). Sheet 1 of 2 No comments. Sheet 2 of 2 1. The resubmittal was not fully responsive to Comment #5 on the first resubmittal; the professional engineer's signature needs to touch the seal. 2. The resubmittal does not appear to be fully responsive to Comment #3 on the first resubmittal; in the fourth bullet of Scope of Work, the number of fasteners per connection (shown as two (2) per connection) does not conform to the detail shown in the revision (one (1) per connection) and the total number of fasteners does not appear to be correct (24 (6x4) would appear to be the correct number rather than the 12 indicated); revise accordingly. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/19/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |