Permit Number: T11BU01335
Parcel: 117080790

Address:
803 S 6TH AV

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T11BU01335
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2013 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized repair submittal for COT ID# 185 at
803 South 6th Avenue (T12BU01335).

Sheet 1 of 2

1. Correct the APN for the subject parcel on the aerial photograph overlay.

2. If the bolts attaching stringers to rooftop structure are to be
replaced, add Exhibit 9, Subsection 2(u) to Billboard Note #9.

Sheet 2 of 2

1. In third bullet of Scope Work, provide depth of the panel sections (in
addition to gauge).

2. Conform the note about light fixture removal from the site to that
contained in the Site Plan (Sheet 1).

3. Provide top and front view detail of the stringer attachment to the
rooftop structure (include cross-section dimensions of the structure
uprights).

4. Clarify if bolts attaching stringers to rooftop structure are to be
replaced, and if so add Exhibit 9, Subsection 2(u) to note below Scope of
Work.

5. In appropriate view or elevation, specify the horizontal spacing
dimensions between the vertical face edges and outer uprights and between
the respective uprights.

6. Provide light mounting detail.

7. Provide standard descriptions of existing lamp and ballast and missing
lighting notes (re point of disconnect and language in Billboard Note #11 on
Sheet 1).

8. In Title Block, revise sheet reference to 2 of 2.


1/10/13
Below are revised comments for the authorized repair resubmittal for COT ID#
185 at 803 South 6th Avenue (T11BU01335). The comments provided on 1/7/13
were based on the original submittal having been provided for review rather
than the resubmittal.

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Conform the note about light fixture removal from the site to that
contained in the Site Plan (Sheet 1).

2. Provide top and front view detail of the stringer attachment to the
rooftop structure uprights, including cross-section dimensions of the
uprights being attached to (in this instance, adding a text note that
specifies the cross-section dimensions and thickness of the uprights is
sufficient).

3. Revise Scope of Work or add note to Stringer/Face Mounting Detail to
clarify that the bolts attaching stringers to rooftop structure uprights are
to be removed and reinstalled and the total number of connections to be
made.

4. In appropriate view or elevation, specify the horizontal spacing
dimensions between the vertical face edges and outer uprights.

5. Provide Professional Engineer's seal and signature (per Exhibit 12,
Section 1(b)(4)).
12/26/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/02/2013 GERARDO BONILLA REJECT SHELF Completed