Permit Number: T11BU01283
Parcel: 11611003H

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T11BU01283
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. PREVIOUS COMMENT; GENERAL: INCLUDE THE INFORMATION SHOWN ON THE 11X17 SHEET ON TO A FULL SIZE DRAWING. THIS IS THE INFORMATION INDICATING THE REINFORCEMENT AND GUNNITE THICKNESS SCHEDULE. THIS DRAWING MUST BE SEALED, SIGNED, AND DATED BY THE ENGINEER OF RECORD.
11/07/2011 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Comment not addressed. All fuel-gas piping and gas-fired appliances within the City of Tucson are within the scope of the 2006 International Fuel Gas Code.
2. Comment not addressed. Show the location of the gas meter on the plans. Reference: Section 106.3.1, IFGC 2006.
3. Comment not addressed. Show the sizes of the pipes serving the proposed gas-fired pool heaters. Reference: Section 402.1, IFGC 2006.
4. Comment not addressed. Provide the total connected load for the gas meter. Reference: Section 402.2, IFGC 2006.
5. Comment not addressed. Specify the materials to be used for the gas piping. Reference: Section 403.1, IFGC 2006.
6. Comment not addressed. Show the source of the water service to the pool area. Reference: Section 106.3.1, IPC 2006.
7. Comment not addressed. Clarify keynotes P6 and P15 on sheet 3.0; how will the potable water supply be protected from backflow? Reference: Section 608.1, IPC 2006.
8. Comment not addressed. Clarify keynote P16 on sheet 3.0; where does this occur? Reference: Section 106.3.1, IPC 2006.
11/07/2011 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Comment not addressed. Provide the listing information for the proposed gas-fired pool heaters. Reference: Sections 301.3, 303.1, and 303.6, IFGC 2006.
2. Comment not addressed. Clarify the nature of the pool equipment enclosure with regard to type (i.e. enclosed yard or roofed structure) and construction materials.
11/08/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Correction comments from last electrical review on 11/03/2011 have not been addressed.
Ray T Majuta
Elect Plan Review
PDSD,CoT
11/09/2011
Ray.majuta@tucsonaz.gov