Permit Review Detail
Review Status: Completed
Review Details: POOL - SPA
Permit Number - T11BU01283
Review Name: POOL - SPA
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/12/2011 | DAVE MANN | FIRE | REVIEW | Approved | |
| 10/24/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: INCLUDE THE INFORMATION SHOWN ON THE 11X17 SHEET ON TO A FULL SIZE DRAWING. |
| 10/31/2011 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide the listing information for the proposed gas-fired pool heaters. Reference: Sections 301.3, 303.1, and 303.6, IFGC 2006. 2. Clarify the nature of the pool equipment enclosure with regard to type (i.e. enclosed yard or roofed structure) and construction materials. |
| 10/31/2011 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. All fuel-gas piping and gas-fired appliances within the City of Tucson are within the scope of the 2006 International Fuel Gas Code. 2. Show the location of the gas meter on the plans. Reference: Section 106.3.1, IFGC 2006. 3. Show the sizes of the pipes serving the proposed gas-fired pool heaters. Reference: Section 402.1, IFGC 2006. 4. Provide the total connected load for the gas meter. Reference: Section 402.2, IFGC 2006. 5. Specify the materials to be used for the gas piping. Reference: Section 403.1, IFGC 2006. 6. Show the source of the water service to the pool area. Reference : Section 106.3.1, IPC 2006. 7. Clarify keynotes P6 and P15 on sheet 3.0; how will the potable water supply be protected from backflow? Reference: Section 608.1, IPC 2006. 8. Clarify keynote P16 on sheet 3.0; where does this occur? Reference: Section 106.3.1, IPC 2006. |
| 11/03/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | No electrical plans have been provided, neesd to provide an electrical plan showing panel,location,load calultions,breaker sizes,conduit and wire sizes to equipment etc. The information provide is to follow Commercial Submittal Requirements which can be located on the City of Tucson Web Site, (under Departments,Planing and Development Services). Ray T Majuta Elect Pln Review PDSD,COT 11/3/11 Rat.majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/04/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 11/04/2011 | SUE REEVES | REJECT SHELF | Completed |