Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T11BU01242
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/30/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 10/12/2011 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Below are comments for the authorized repair submittal for COT ID# 11 at 2451 East Benson Highway (T11BU01242). Sheet 1 of 2 No comments. Sheet 2 of 2 1. Provide correct height and correct crossover/handrail location on west face elevation. 2. Note specifically which three wood section panels are removed from the west face (lateral location on that face side).. 3. Indicate on plan sheet reason wood panel sections were removed without a permit and the current location of the removed panel sections. 4. If plan is approved, staff add notation on permit and/or plan sheet that issuance of permit for replacement of part removed from installed position not to set precedent for other applications where parts have been removed without permit. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/13/2011 | CINDY AGUILAR | OUT TO CUSTOMER | Completed |