Permit Number: T11BU01241
Parcel: 99999999B

Address:
7100 S I19

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T11BU01241
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/29/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
10/12/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized repair submittal for COT ID# 568 at
7100 South Interstate 19 (T11BU01241).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Note specifically which wood section panel is removed (face side and
location on that face side).

2. Indicate which of the two face elevations is being depicted (appears to
be north from crossover location; rather than add second elevation, the note
may indicate that south face configuration is same as to wood sections,
aprons and stringers depicted).

3. Indicate on plan sheet reason wood panel section was removed without a
permit and the current location of the removed panel section.

4. If plan is approved, staff add notation on permit and/or plan sheet that
issuance of permit for replacement of part removed from installed position
not to set precedent for other applications where parts have been removed
without permit.