Permit Number: T11BU01240
Parcel: 140420400

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T11BU01240
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/30/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
10/12/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized repair submittal for COT ID# 261 at
2334 East Valencia Road (T11BU01240).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Clarify if wood panel sections are to be replaced on both faces.

2. Add second crossover/handrail to elevation and clarify that elevation is
same for both faces (if wood panel sections are to be replaced on both
faces; otherwise specify the face).

3. Note specifically which three wood section panels are removed (face side
and location on that face side).

4. Indicate on plan sheet reason the three wood panel sections were removed
without a permit and the current location of the removed panel sections.

5. If plan is approved, staff add notation on permit and/or plan sheet that
issuance of permit for replacement of part removed from installed position
not to set precedent for other applications where parts have been removed
without permit.