Permit Number: T11BU01159
Parcel: 99999999B

Address:
851 E 22ND ST

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T11BU01159
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/10/2012 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
03/08/2012 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized repair resubmittal for COT ID# 61 at
851 East Speedway Boulevard (T11BU01159).

Sheet 1

No comments.

Sheet 2A

1. Complete the revised dimensionality as to catwalk placement on the
support ledgers to show the location of the J-bolt holes and/or catwalk
edges relative to the ledger ends (alternatively, this dimensionality may be
provided in the detail on Sheet 2b).

2. Revise the added note on bringing the support I-beams into plumb to
clarify that backfill will only consist of earth removed and that the
I-beams are not to be removed from their footing and reinstalled.

3. Provide detailed dimensions for each of the existing and proposed
replacement uprights, including the length; the cross-section dimensionss,
and the thicknesses of the web, vertical side pieces, and horizontal support
flange.

Sheet 2B

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/29/2012 CPIERCE1 OUT TO CUSTOMER Completed