Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T11BU01159
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/10/2012 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 03/08/2012 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Below are comments for the authorized repair resubmittal for COT ID# 61 at 851 East Speedway Boulevard (T11BU01159). Sheet 1 No comments. Sheet 2A 1. Complete the revised dimensionality as to catwalk placement on the support ledgers to show the location of the J-bolt holes and/or catwalk edges relative to the ledger ends (alternatively, this dimensionality may be provided in the detail on Sheet 2b). 2. Revise the added note on bringing the support I-beams into plumb to clarify that backfill will only consist of earth removed and that the I-beams are not to be removed from their footing and reinstalled. 3. Provide detailed dimensions for each of the existing and proposed replacement uprights, including the length; the cross-section dimensionss, and the thicknesses of the web, vertical side pieces, and horizontal support flange. Sheet 2B No comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/29/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |