Permit Number: T11BU01141
Parcel: 12809016D

Address:
4701 E 22ND ST

Review Status: Completed

Review Details: GRADING

Permit Number - T11BU01141
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2011 TERRY STEVENS ZONING REVIEW Denied
09/21/2011 LOREN MAKUS ENGINEERING REVIEW Denied September 26, 2011
T11CM02851/T11BU01141
Site and Grading
Circle K at Swan and 22nd

The site and grading plans are not approved as submitted. Please address the following

1. Confirm the project description in the drainage report. Also check the general comments on the plan sheets for typos and artifacts from other projects.

2. The drainage report doesn't seem to take the storm drain system in 22nd Street. Provide discussion of how the storm drains affect the project site. According to the GIS map, a storm drain in 22nd street collects street flows Rosemont Avenue and discharges into wash A.


3. The maximum driveway width at the property line is 30 feet.. Revise the site plan accordingly. ( City Code 25-39)

4. Provide clarification with additional slope indicators to demonstrate onsite watersheds will be directed to the water harvesting areas as indicated on the water harvesting plan.

5. Clearly label all curb radii. Demonstrate the curb returns have a 25-foot radius in accordance with the Transportation access management guidelines.

6. The PDSD GIS map shows storm drain catch basins in the right of way adjacent to the project site. Revise the SWPPP to address control of fugitive sediment relative to the catch basins.


Loren Makus, EIT
Senior Engineering Associate
Loren.makus@tucsonaz.gov
10/04/2011 ANDREW CONNOR NPPO REVIEW Denied Site plan approval in necessary to continue review

Ensure that all Engineering comment and concerns are addressed.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/20/2011 GERARDO BONILLA OUT TO CUSTOMER Completed
10/20/2011 SUE REEVES REJECT SHELF Completed