Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T11BU01091
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2011 | MARTIN BROWN | FIRE | REVIEW | Denied | Fire Comments: Sheet A100 1. Provide seal on this sheet. Building Data and Egress are profession practice. 2. Show locations of fire hydrants. See IFC Sections 508 and Appendix B for fire flow for new area. 3. Show fire lanes. Show locations of gates, etc. Arials show the site as congested. Fire lanes may need signs. See IFC Section 503 as amended. 4. Provide quantities of hazardous materials. Will they increase with this addition? See IFC Chapter 27. |
| 08/24/2011 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 09/15/2011 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET S2.0 (ROOF FRAMING PLAN); STRUCTURAL CALCULATIONS (PAGE 10): THE CALCULATIONS INDICATE A 12X3.0 Z 14 GAGE JOIST, WHILE THE PLAN INDICATES A 10X3X14 GAGE Z JOIST. CLARIFY. 2. GENERAL: SHOULD A LATERAL ANALYSIS BE PROVIDED FOR THIS PROJECT? VERIFY. |
| 09/16/2011 | TERRY STEVENS | ZONING | REVIEW | Denied | Provide a copy of the approved site plan with next submittal. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 09/19/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |
| 09/19/2011 | SUE REEVES | REJECT SHELF | Completed |