Permit Number: T11BU01091
Parcel: 13225066A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T11BU01091
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/24/2011 MARTIN BROWN FIRE REVIEW Denied Fire Comments:

Sheet A100

1. Provide seal on this sheet. Building Data and Egress are profession practice.

2. Show locations of fire hydrants. See IFC Sections 508 and Appendix B for fire flow for new area.

3. Show fire lanes. Show locations of gates, etc. Arials show the site as congested. Fire lanes may need signs. See IFC Section 503 as amended.

4. Provide quantities of hazardous materials. Will they increase with this addition? See IFC Chapter 27.
08/24/2011 JASON GREEN ENGINEERING REVIEW Approved
09/15/2011 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S2.0 (ROOF FRAMING PLAN); STRUCTURAL CALCULATIONS (PAGE 10): THE CALCULATIONS INDICATE A 12X3.0 Z 14 GAGE JOIST, WHILE THE PLAN INDICATES A 10X3X14 GAGE Z JOIST. CLARIFY.
2. GENERAL: SHOULD A LATERAL ANALYSIS BE PROVIDED FOR THIS PROJECT? VERIFY.
09/16/2011 TERRY STEVENS ZONING REVIEW Denied Provide a copy of the approved site plan with next submittal.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/19/2011 CPIERCE1 OUT TO CUSTOMER Completed
09/19/2011 SUE REEVES REJECT SHELF Completed