Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T11BU00880
Parcel: 99999999S

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T11BU00880
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/01/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
08/01/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized repair submittal for COT ID# 14 at
3098 East Irvington Road (T11BU00880).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Indicate the overall length of catwalk ledgers and distance ledgers
protrude from beam faces.

2. Indicate width of catwalks and catwalk positions relative to ledgers
(from beam face and outer ledger edge).

3. Provide trade or manufacturer's reference identifying grade of catwalk
grating.

4. Clarify if safety cable and mounting to catwalk exists and, if so, if to
be removed and reinstalled with the catwalk or replaced.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/05/2011 SUE REEVES OUT TO CUSTOMER Completed