Review Details: BILLBOARD - BLDG30days
Permit Number - T11BU00880
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/01/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 08/01/2011 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Below are comments for the authorized repair submittal for COT ID# 14 at 3098 East Irvington Road (T11BU00880). Sheet 1 of 2 No comments. Sheet 2 of 2 1. Indicate the overall length of catwalk ledgers and distance ledgers protrude from beam faces. 2. Indicate width of catwalks and catwalk positions relative to ledgers (from beam face and outer ledger edge). 3. Provide trade or manufacturer's reference identifying grade of catwalk grating. 4. Clarify if safety cable and mounting to catwalk exists and, if so, if to be removed and reinstalled with the catwalk or replaced. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/05/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |