Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11BU00854
Parcel: 99999999S

Address:
2556 E GRANT RD

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T11BU00854
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/23/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
07/29/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments Updated/corrected

Below are comments for the authorized repair submittal for COT ID# 438 at
2560 East Grant Road (T11BU00854).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Redline with correct dimension for lower spacers on Typical Section Thru
Sign (6"x4"x1").



Please disregard the following

Below are comments for the authorized repair submittal for COT ID# 14 at
3098 East Irvington Road (T11BU00880).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Indicate the overall length of catwalk ledgers and distance ledgers
protrude from beam faces.

2. Indicate width of catwalks and catwalk positions relative to ledgers
(from beam face and outer ledger edge).

3. Provide trade or manufacturer's reference identifying grade of catwalk
grating.

4. Clarify if safety cable and mounting to catwalk exists and, if so, if to
be removed and reinstalled with the catwalk or replaced.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/01/2011 CPIERCE1 OUT TO CUSTOMER Completed