Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD - BLDG30days
Permit Number - T11BU00853
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/23/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 07/13/2011 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Below are comments for the authorized repair submittal for COT ID# 272 at 3898 East Valencia Road (T11BU00853). Sheet 1 of 2 No comments. Sheet 2 of 2 1. Revise east face elevation to show existing metal trim with 45 degree mitered corners; add note to west face elevation that wood trim configuration is for east face replacement as well as west existing & replacement. 2. Add note that length dimension provided for existing metal trim in Scope of Work is for the outer edge (inner edge is 11' 4"). 3. Revise dimensions shown for two lower spacers per face to match 3" x 4" stringer & existing (6" x 4" x 1"). 4. Revise Typical Section thru Sign to show spacer width and top and bottom stringers protruding further from beam than the middle four stringers and/or add appropriate details. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/05/2011 | SUE REEVES | OUT TO CUSTOMER | Completed |