Permit Number: T11BU00800
Parcel: 126070020

Review Status: Active

Review Details: TANKS

Permit Number - T11BU00800
Review Name: TANKS
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2011 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T11BU00800
Propane Tank and Dispenser

Provide specification sheets for dispenser,emergency shut off switch.
Indicate an equipment ground in new circuit, provide circuit breaker size at panel.
Indicate if any conduit will be under a driveway or parking area requiring 24" burial debth.

Ray Majuta,
PDSD, City of Tuc,
Elect Plan Ck,
7/18/11

Final Status

Task End Date Reviewer's Name Type of Review Description
07/19/2011 SUE REEVES REJECT SHELF RECEIVED