Permit Number: T11BU00768
Parcel: 99999999B

Address:
640 E 22ND ST

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T11BU00768
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/15/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
06/23/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the authorized repair submittal for COT
ID# 60 at 640 East 22nd Street (T11BU00768).

Sheet 1 of 2

No comments.

Sheet 2 of 2

1. Provide Indemnification Agreement required by Subparagraph 9.4 of the
Stipulation.

2. Indicate the overall length of catwalk ledgers and distance ledgers
protrude from beam faces.

3. Indicate width of catwalks and catwalk positions relative to ledgers
(from beam face and outer ledger edge).

4. Provide trade or manufacturer's reference identifying grade of catwalk
grating.

5. Clarify in Scope of Work if safety cable and mounting are to be removed
and reinstalled or replaced.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/30/2011 CINDY AGUILAR OUT TO CUSTOMER Completed
08/30/2011 SUE REEVES REJECT SHELF Completed