Permit Number: T11BU00470
Parcel: 12801033A

Address:
6211 E 22ND ST

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T11BU00470
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
04/28/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized repair submittal for COT ID #90 at 6211
East 22nd Street (T11BU00470).

1. Clarify whether the top stringer on the east face is to be replaced or
removed and reinstalled. [Note: the top stringer is typically 3" x 6" x 24'
and the second stringer from the top is typically 3" x 4" x 24'].

2. The Typical Section Thru Sign designates the top and bottom stringers as
"spacers", but does not depict the 6" x 6" spacers referenced as being
replaced in the Scope of Work; redesignate the top stringer, depict the
spacers (typically located between the top stringer and upright), and
include spacer thickness where dimensions are referenced.

3. Indicate existing and any replacement fasteners attaching the top
stringer and spacers to the existing upright.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/03/2011 CPIERCE1 OUT TO CUSTOMER Completed