| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/26/2011 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 04/28/2011 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Denied | BRC Comments Below are comments on the authorized repair submittal for COT ID #90 at 6211 East 22nd Street (T11BU00470). 1. Clarify whether the top stringer on the east face is to be replaced or removed and reinstalled. [Note: the top stringer is typically 3" x 6" x 24' and the second stringer from the top is typically 3" x 4" x 24']. 2. The Typical Section Thru Sign designates the top and bottom stringers as "spacers", but does not depict the 6" x 6" spacers referenced as being replaced in the Scope of Work; redesignate the top stringer, depict the spacers (typically located between the top stringer and upright), and include spacer thickness where dimensions are referenced. 3. Indicate existing and any replacement fasteners attaching the top stringer and spacers to the existing upright. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/03/2011 | CPIERCE1 | OUT TO CUSTOMER | Completed |