Permit Number: T11BU00468
Parcel: 122010810

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T11BU00468
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
04/28/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments on the authorized repair submittal for COT ID #370 at
4045 East Speedway Boulevard (T11BU00468).

Sheet 1 of 1

No comments.

Sheet 2 of 2

1. Clarify the cross-section dimensions of the existing and replacement
backrails (shown as 2"x 6" in Backrail Mounting Detail and 3" x 4"
elsewhere).

2. Depict the backrail on an elevation, showing the 14-foot length to be
replaced and any lengths that are remaining and not to be replaced.

3. In Stringer Between Uprights, it appears that the orientation of the
stringer does not match existing and #12 screws referenced do not currently
exist; rotate the orientation to match existing and delete the #12 screws
shown there and referenced in the second note of Scope of Work.

4. Clarify the apron sections fasteners (shown as 16d nails in Scope of
Work and as #12 screws in Apron Mounting Detail).

Final Status

Task End Date Reviewer's Name Type of Review Description
05/03/2011 CPIERCE1 OUT TO CUSTOMER Completed