04/26/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
04/28/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Below are comments on the authorized repair submittal for COT ID #329 at
1110
East Broadway Boulevard (T11BU00465).

1. Clarify whether the top stringer on the east face is to be replaced or
removed and reinstalled.

2. The Typical Section Thru Sign designates the top and bottom stringers as
"spacers", but does not depict the 6" x 6" x 1" spacers referenced as being
replaced in the Scope of Work; redesignate the top stringer and depict the
spacers (typically located between the top stringer and upright).

3. Indicate existing and any replacement fasteners attaching the top
stringer and spacers to the existing upright.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/03/2011 CPIERCE1 OUT TO CUSTOMER Completed