Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11BU00465
Parcel: 99999999B

Review Status: Completed

Review Details: BILLBOARD - BLDG30days

Permit Number - T11BU00465
Review Name: BILLBOARD - BLDG30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/26/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Needs Review
04/28/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied Below are comments on the authorized repair submittal for COT ID #329 at
1110
East Broadway Boulevard (T11BU00465).

1. Clarify whether the top stringer on the east face is to be replaced or
removed and reinstalled.

2. The Typical Section Thru Sign designates the top and bottom stringers as
"spacers", but does not depict the 6" x 6" x 1" spacers referenced as being
replaced in the Scope of Work; redesignate the top stringer and depict the
spacers (typically located between the top stringer and upright).

3. Indicate existing and any replacement fasteners attaching the top
stringer and spacers to the existing upright.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/03/2011 CPIERCE1 OUT TO CUSTOMER Completed