Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T11BU00179
Parcel: 136242320

Address:
3152 S KOLB RD

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/ZONING-WALKTHRU

Permit Number - T11BU00179
Review Name: RESIDENTIAL - BLDG/ZONING-WALKTHRU
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/22/2011 DAVID RIVERA ZONING REVIEW Denied DDO or BOA Comments

FROM: David Rivera,
Principal Planner
Zoning Review Section

PROJECT: Activity No.: T11BU00179
Address: 3152 S Kolb Road
Project: 3 Car Carport, single car Carport, and Attached porch

Board of Adjustment variances required.
See below

TRANSMITTAL: 09/08/2011

COMMENTS: The following comments have been made for the subject property and the required variances.

1) This review is for a Single Family Development site in the R-2 Zone (LUC Section 6.3.8). The Development Designator is "I" (LUC Section 2.3.5.2.A.1) and the Perimeter Yard Indicator is AA (LUC Section 3.2.6.4).

2) The plans depict a new 3-car carport constructed along the street perimeter (Kolb Road) a distance of 13'-7" from the existing property line. The required setback for the carport is 18 feet from the property line and one (1) foot from the back of sidewalk. The existing condition is 13'-7 " from the property line, LUC section 3.2.6.5.B.2.a.1 and .2 A DDO shall be required for the [the building setback east property line. The minimum setback is 18 feet from PL. east property line.

3) The side porch or covered patio is depicted in the north building setback at 6" from the north property line. The required setback is the greatest of 6 feet or 2/3 of the height of the structure. LUC section 3.2.6.4 -AA perimeter yard indicator table.

4) The side single car carport or covered patio is depicted in the south building setback at 6" south yard property line. The required setback is the greatest of 6 feet or 2/3 of the height of the structure. LUC section 3.2.6.4 -AA perimeter yard indicator table.

5) Please be aware that additional comments shall be necessary relative to additional information provided with the next submittal.
12/29/2011 JASON GREEN ENGINEERING REVIEW Approved
12/29/2011 GBONILL1 NPPO REVIEW Needs Review
12/29/2011 GBONILL1 BUILDING-RESIDENTIAL REVIEW Needs Review