Permit Review Detail
Review Status: Completed
Review Details: TANKS
Permit Number - T11BU00120
Review Name: TANKS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/01/2011 | DAVE MANN | FIRE | REVIEW | Denied | Fire Comments: Sheet XF 101 1. New cut sheets are required for this projects tanks, piping, etc. Provide listings per IFC Chapters 34 and 22. Sheets XF 102 and XF 301 1. Show the locations of the emergency shut offs required by IFC 2203. Sheets XF 202 and XF 207 1. Plans show a 4" minimum curb around dispensers. A 6" curb is required by IFC Section 2206.7.3. |
| 02/07/2011 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/16/2011 | TERRY STEVENS | ZONING | REVIEW | Denied | 02/16/2011 Development Services Department Zoning Review Section Terry Stevens Lead Planner Comments: 1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed. 2. Zoning could not verify that the building plan was in compliance with the approved development plan. Please submit two copies of the approved and stamped development, landscape, and NPPO plans with the next building plan submittal. 3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved site/development plan. Additional comments may be forthcoming. |