Permit Number: T10PL01581
Parcel: 13323164A

Review Status: Completed

Review Details: PLUMBING

Permit Number - T10PL01581
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/15/2010 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Any fitting or connection in a drainage system that results in a reduction of the pipe area is prohibited (e.g. 6" x 4" reducer fitting). Reference: Section 316.4.1, UPC 2006.
2. Provide listing information for the oil interceptor. Reference: Section 301.1.1, UPC 2005.
10/20/2010 GBONILL1 WWM REVIEW Needs Review