Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Plan Number: T10PI00014
Parcel: Unknown

Review Status: Completed

Review Details: PIA - RESUBMITTAL

Plan Number - T10PI00014
Review Name: PIA - RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/13/2012 JOSE ORTIZ DOT TRAFFIC REVIEW Denied March 1, 2012
ACTIVITY NUMBER: T10PI00014
PROJECT NAME: WalMart-Houghton
PROJECT ADDRESS: Houghton - Golf Links
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal. The following items must be revised or added to the plan.
Include a response letter with the next submittal that states how all comments have been addressed.

See redlines on sheets 6 and 7 in the submitted drawings and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.



If you have any questions, I can be reached at 837-6730 or Jose.Ortiz@tucsonaz.gov
03/13/2012 RICHARD LEIGH DOT ENGINEERING REVIEW Denied March 12, 2012

SUBJECT: HOUGHTON ROAD AND GOLF LINKS ROAD, WALMART I-2010-019 T10PI00014, 1st Rev.

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

Permits and Codes Section has reviewed the PIA plan set for the subject project and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal. Please provide a written response to each comment and return red line drawings with re-submittal.


1. Sheet 1, Flood Zone Designation : Reference current FEMA FIRM panels.

2. Sheet 2, Asphalt Pavement Detail: Revise detail to show correct pavement thickness and reference PC/COT Standard Specifications for Public Improvements (SSPI) for compaction and testing requirements.

3. Sheet 2, Thickened Pavement Edge Detail: Revise detail to show correct pavement section thickness.

4 Sheet 2, Detail A/2: Revise detail to show proposed median Island.

5. Sheet 3, Houghton Rd. driveway entrance: Indicate the curb type for the south curb return and indicate the placement of a curb terminal section Per PC/COT S.D. 212 at end of the return.

6. Sheet 3: Label delineated Temporary Roadway Easement with recordation information. Additionally, submit a copy of the easement with next submittal.

7. Sheet 3: Provide Beginning and ending stations for the proposed guardrail along Houghton Road.

8. Sheet 8: Lighten shading for asphalt pavement so lettering is clearly legible.

9. Sheet 8, Accessible Ramp Sidewalk Detail: Revise detail to reference SSPI testing requirements.

10. Sheet 9: Indicate slope treatment for the cut slope along Golf Links Road.

11. Sheet 9: Include all lines used in drawing in legend.

12. Sheet 9: Provide complete storm drain details for all storm drain structures proposed in the public right-of-way in this drawing.

13. Place a note on drawing indicating that the owner of the property is responsible for the maintenance, repair and blue staking of the onsite drainage facilities located in the public right-of-way.

14. Indicate that all curb access ramps, except on the north ramp located at the Houghton Rd. driveway entrance, will have a vertical curb backstop placed per PC/COT S.D. 207 to restrict vehicular access.

15. Revise sheet numbering on the Landscaping sheets to be sequential with offsite improvement plan sheets.

16. Submit approved development plan with next submittal.

Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsonaz.gov
03/30/2012 GARY WITTWER DOT LANDSCAPE REVIEW Passed
03/30/2012 BLANCA ESPINO PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
03/30/2012 BLANCA ESPINO PIA COORDINATOR OUT TO CUSTOMER Completed