Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Plan Review Detail
Review Status: Completed
Review Details: PIA SUBMITTAL
Plan Number - T10PI00010
Review Name: PIA SUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/23/2010 | LANCE PETERSON | DOT STREET MAINTENANCE | REVIEW | Denied | Show spot elevation at the bus bay curb to verify for standing water issue. |
| 07/23/2010 | RICHARD LEIGH | DOT ENGINEERING | REVIEW | Denied | July 22, 2010 SUBJECT: Broadway Boulevard, Scott Avenue & 6th Avenue, PIA T10PI0010, U-2010-006 PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal. 1. Include the plan number "U-2010-006" in title block of each sheet. 2. Include Development Services Department PIA activity number (T10PI0010) on cover sheet. 3. Clearly indicate where concrete pavers and concrete will be used for sidewalk. 4. Show all improvements proposed on 12th Street. Refer to redline plans for additional comments and comment details. If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsoz.gov |
| 07/26/2010 | RLEIGH1 | UTILITY CLEARANCES | COT STREETS DIVISION | Completed | |
| 07/26/2010 | RLEIGH1 | UTILITY CLEARANCES | COT WATER NEW DEVELOPMENT | Completed | |
| 07/26/2010 | RLEIGH1 | UTILITY CLEARANCES | PC WASTEWATER MGMT | Completed | |
| 07/26/2010 | RLEIGH1 | UTILITY CLEARANCES | QUEST COMMUNICATION | Completed | |
| 07/26/2010 | RLEIGH1 | UTILITY CLEARANCES | TUCSON ELECTRIC POWER CO | Completed | |
| 07/26/2010 | RLEIGH1 | UTILITY CLEARANCES | COX COMMUNICATION | Completed | |
| 07/26/2010 | RLEIGH1 | UTILITY CLEARANCES | SOUTHWEST GAS CORP | Completed | |
| 07/26/2010 | RLEIGH1 | UTILITY CLEARANCES | EL PASO NATURAL GAS | Completed | |
| 07/26/2010 | RLEIGH1 | UTILITY CLEARANCES | KINDER MORGAN ENERGY | Completed | |
| 07/27/2010 | GARY WITTWER | DOT LANDSCAPE | REVIEW | Denied | Please re-install the sleeving as originally designed on both Scott Ave and Broadway. |
| 07/28/2010 | JOSE ORTIZ | DOT TRAFFIC | REVIEW | Denied | July 28, 2010 ACTIVITY NUMBER: T10PI00010 PROJECT NAME: Unisource Energy PROJECT ADDRESS: Broadway/Scott PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal. The following items must be revised or added to the plan. Include a response letter with the next submittal that states how all comments have been addressed. 1. See redlines on the submitted drawings and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes. 2. Along 6th Avenue ensure that all existing signs that are effected by the off-site improvements and are applicable to the roadway remain in place or relocated to an appropriate location. If damaged or unsuitable for reuse then replace with new sign and/or post. See redlines for clarification. 3. Place the PIA and CDRC Case number on the cover sheet. 4. Add the following Signing General Notes 1 through 5(b) per PCDOT & TDOT Signing Manual (2002) (Chapter 1, Sheet 12) to the Plans. 5. Add the following Pavement Marking/Striping General Notes to the Plans: 'ALL STREET STRIPING & SIGNAGE TO BE COORDINATED WITH C.O.T. TRAFFIC ENGINEERING CALL 791-4259 A MINIMUM OF 48 HOURS PRIOR TO THE INSTALLATION OR REMOVAL OF ANY SIGNAGE OR STRIPING. ALL REQUIRED STRIPING AND SIGNAGE WILL BE INSTALLED AT THE CONTRACTOR'S EXPENSE. NEW STRIPING TO BE THERMOPLASTIC MATERIAL. USE 2" SQUARE-TUBE POST AND SQUARE TUBE POST FOUNDATIONS FOR SIGNING. BARRICADE PLAN MUST BE SUBMITTED TO THE CITY OF TUCSON TRAFFIC ENGINEERING FOR APPROVAL 48 HOURS IN ADVANCE OF ANY WORK IN PUBLIC RIGHT OF WAY.' 'THE CITY SHALL NOT BE LIABLE FOR ANY ERRORS AND/OR OMISSIONS ON THESE PLANS. ITEMS NOT MEETING CITY STANDARDS SHALL BE REPAIRED/REPLACED BY THE DEVELOPER/CONTRACTOR AND AT NO COST TO THE CITY.' 'ALL WARNING SIGN PANELS SHALL BE FLUORESCENT YELLOW DIAMOND-GRADE (DG-CUBED OR EQUIVALENT) SHEETING. ALL OTHER SIGN PANELS SHALL HAVE HIGH INTENSITY PRISMATIC TYPE IV SHEETING.' If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov |
| 07/29/2010 | RICHARD LEIGH | PIA COORDINATOR | CUSTOMER CALLED; PLANS @ AMBASSSADOR | Completed | |
| 07/29/2010 | RICHARD LEIGH | PIA COORDINATOR | OUT TO CUSTOMER | Completed |