Plan Number: T10PI00008
Parcel: Unknown

Address:
7501 S KOLB RD

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T10PI00008
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/13/2010 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Denied provide maitenance access to drainage structure
provide spillway (gabion) with towdown for the flow going into Julian wash
05/17/2010 GARY WITTWER DOT LANDSCAPE REVIEW Denied Please address the Native Plant Preservation Ordinance. If it has already been address, please submit a copy of the approved plan.
06/01/2010 JOSE ORTIZ DOT TRAFFIC REVIEW Denied June 1, 2010
ACTIVITY NUMBER: T10PI00008
PROJECT NAME: Julian Wash Greenway
PROJECT ADDRESS: 7501 S Kolb Rd
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal. The following items must be revised or added to the plan. Include a response letter with the next submittal that states how all comments have been addressed.

1. See redlines on the submitted drawings and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.

2. Along Kolb Road ensure that all existing signs that are effected by the off-site improvements and are applicable to the roadway remain in place or relocated to an appropriate location. If damaged or unsuitable for reuse then replace with new sign and/or post.

3. The private roadway has a proposed radius of 50' - TDOT-Traffic prefers a radius return of 25' a radius larger then 25' will need to be justified based on the use and/or field conditions surrounding the private roadway.

4. Show existing striping in plan view to establish the location of pavement marking obliteration.

5. Install street names under the proposed stop sign at the proposed private roadway off of Kolb Road per PCDOT & TDOT Signing Manual (2002) Chap 5-11, 5-12, and Chap 9-2.

6. If applicable install a W14-2a (No Outlet) or W14-1a (Dead end) plaque beneath the street name signs.

7. Provide dimensions or a typical section illustrating the width of the private road and adjacent path.

8. Place the PIA and CDRC Case number on the cover sheet.



If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
06/07/2010 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Completed
06/07/2010 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
06/07/2010 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
06/07/2010 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Completed
06/07/2010 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
06/07/2010 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Completed
06/07/2010 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
06/07/2010 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Completed
06/07/2010 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed
06/08/2010 RICHARD LEIGH DOT ENGINEERING REVIEW Denied June 8, 2010

SUBJECT: Julian Wash Greenway

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal.

1. Include the plan number "I-2010-014" in the title block of each sheet.

2. Include Development Services Department PIA activity number "T01PI00008"on cover sheet.

3. Provide hydraulic analysis for sizing of catch basin and culvert within the public right-of-way.

4. Will scour protection be provided where channel discharges into the Julian Wash?

5. If a flood plain use permit was issued for this project please include FUP# in general notes. "Floodplain Use Permit No._______, has been issued by Development Services Department for work impacting City and/or FEMA Floodplains."

6. Provide barricade railing around drop structure located at +/- 13+60, RT (Kolb Rd).

7. Provide a removable post barricades at the entrance of pedestrian pathway to restrict vehicular traffic.

8. Indicate the proposed composition of pathway.

Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsonaz.gov
06/08/2010 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
06/08/2010 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed