Plan Number: T10PI00003
Parcel: Unknown

Address:
5301 E GRANT RD

Review Status: Completed

Review Details: PIA SUBMITTAL

Plan Number - T10PI00003
Review Name: PIA SUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2010 JOSE ORTIZ DOT TRAFFIC REVIEW Denied February 22, 2010
ACTIVITY NUMBER: T10PI00003
PROJECT NAME: Craycroft-TMC
PROJECT ADDRESS: Craycroft - Grant
PROJECT REVIEWER: Jose E. Ortiz PE, Traffic Engineer

Resubmittal Required: Traffic Engineering does not recommend approval of the PIA Plan; therefore a revised PIA Plan is required for re-submittal. The following items must be revised or added to the plan.

1. Include a response letter with the next submittal that states how all comments have been addressed.

2. See redlines on the submitted drawings and address the additional redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.

3. Along Craycroft Road ensure that all existing signs that are effected by the off-site improvements and are applicable to the roadway remain in place or relocated to an appropriate location. If damaged or unsuitable for reuse then replace with new sign and/or post.

4. Install R1-1 (Stop Sign) at the proposed driveway entering this development per PCDOT & TDOT Signing Manual (2002) Chap 5-11, 5-12, and Chap 9-2.

5. Provide a 'RIGHT LANE' (R3-5F) supplemental plaque under the new (R3-5R).

6. Place the PIA and CDRC Case number on the cover sheet.

7. Add the Pavement Marking General Notes per PCDOT & TDOT Pavement Marking Design Manual (2208) Sheet 2-1

8. Add the following Signing General Notes 5(a) & 5(b) per PCDOT & TDOT Signing Manual (2002) (Chapter 1, Sheet 12) to the Plans.

9. Add the following Pavement Marking/Striping General Notes to the Plans:

'ALL STREET STRIPING & SIGNAGE TO BE COORDINATED WITH C.O.T. TRAFFIC ENGINEERING CALL 791-4259 A MINIMUM OF 48 HOURS PRIOR TO THE INSTALLATION OR REMOVAL OF ANY SIGNAGE OR STRIPING. ALL REQUIRED STRIPING AND SIGNAGE WILL BE INSTALLED AT THE CONTRACTOR'S EXPENSE. NEW STRIPING TO BE THERMOPLASTIC MATERIAL. USE 2" SQUARE-TUBE POST AND SQUARE TUBE POST FOUNDATIONS FOR SIGNING. BARRICADE PLAN MUST BE SUBMITTED TO THE CITY OF TUCSON TRAFFIC ENGINEERING FOR APPROVAL 48 HOURS IN ADVANCE OF ANY WORK IN PUBLIC RIGHT OF WAY.'

'ALL NON-SIGNALIZED INTERSECTION STREET NAMES MUST HAVE E-W BLOCK NUMBER ADDRESSES FOR E-W ROADWAYS AND N-S BLOCK NUMBER ADDRESSES FOR N-S ROADWAYS.'

'THE CITY SHALL NOT BE LIABLE FOR ANY ERRORS AND/OR OMISSIONS ON THESE PLANS. ITEMS NOT MEETING CITY STANDARDS SHALL BE REPAIRED/REPLACED BY THE DEVELOPER/CONTRACTOR AND AT NO COST TO THE CITY.'

'ALL WARNING SIGN PANELS SHALL BE FLUORESCENT YELLOW DIAMOND-GRADE (DG-CUBED OR EQUIVALENT) SHEETING. ALL SCHOOL ZONE SIGNS SHALL BE FLUORESCENT YELLOW-GREEN DIAMOND GRADE (DG-CUBED OR EQUIVALENT) SHEETING. ALL OTHER SIGN PANELS SHALL HAVE HIGH INTENSITY PRISMATIC TYPE IV SHEETING.'


If you have any questions, I can be reached at 791-4259 x76730 or Jose.Ortiz@tucsonaz.gov
03/03/2010 RICHARD LEIGH DOT ENGINEERING REVIEW Approv-Cond 1. Include the plan number "U-2010-003" in the title block of each sheet.

2. Include Development Services Department PIA activity number "T01PI00003"on cover sheet.
03/10/2010 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved no objection pertaining to Street Maintenance (Right Turn lane Improvement)- 02/22/2010
03/16/2010 GARY WITTWER DOT LANDSCAPE REVIEW Approv-Cond Need to see approve NPPO submittal.
03/18/2010 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSSADOR Completed
03/18/2010 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed
04/16/2010 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Completed
04/16/2010 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Completed
04/16/2010 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Completed
04/16/2010 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Completed
04/16/2010 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Completed
04/16/2010 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Completed
04/16/2010 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Completed
04/16/2010 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Completed
04/16/2010 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Completed