Plan Number: T10PI00001
Parcel: Unknown

Address:
3434 S KINO PW

Review Status: Completed

Review Details: PIA RESUBMITTAL

Plan Number - T10PI00001
Review Name: PIA RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2010 RLEIGH1 UTILITY CLEARANCES COT STREETS DIVISION Approved
02/22/2010 RLEIGH1 UTILITY CLEARANCES COT WATER NEW DEVELOPMENT Approved
02/22/2010 RLEIGH1 UTILITY CLEARANCES PC WASTEWATER MGMT Approved
02/22/2010 RLEIGH1 UTILITY CLEARANCES QUEST COMMUNICATION Approved
02/22/2010 RLEIGH1 UTILITY CLEARANCES TUCSON ELECTRIC POWER CO Approved
02/22/2010 RLEIGH1 UTILITY CLEARANCES COX COMMUNICATION Approved
02/22/2010 RLEIGH1 UTILITY CLEARANCES SOUTHWEST GAS CORP Approved
02/22/2010 RLEIGH1 UTILITY CLEARANCES EL PASO NATURAL GAS Approved
02/22/2010 RLEIGH1 UTILITY CLEARANCES KINDER MORGAN ENERGY Approved
02/26/2010 RICHARD LEIGH DOT ENGINEERING REVIEW Denied February 26, 2010

SUBJECT: Tucson Marketplace Boulevard & Kino Parkway, PIA T10PI0001

PROJECT REVIEWER: Richard Leigh, DOT, Permits and Codes Section

RESUBMITTAL REQUIRED: Permits and Codes Section has reviewed the PIA Plan and does not recommend approval of the PIA Plan at this time. The following comments need to be addressed in the next submittal.

1. A slope easement will be required for the proposed slopes along Tucson Marketplace Boulevard that are adjacent to private property.

2. Provide placeholders for easement recordation information so recordation information can be added when obtained.

3. Sheet 2, Roadway Cross Section Details: Show slopes adjacent to roadway and indicate a 2' buffer, with a cross slope no steeper than 2%, between sidewalk and slope hinge point.

4. Sheet 12, Crosswalk Through Median Detail: Indicate the placement of truncated domes in median crosswalk area.

Refer to redline plans for additional comments and comment details.

If you have any questions, I can be reached at 837-6647 or Richard.Leigh@tucsonaz.gov
03/01/2010 JOSE ORTIZ DOT TRAFFIC REVIEW Denied See Redlines. Contact Jose Ortiz or Matthew Geweke with questions regarding the redline comments. During the next submittal please re-submit the roll of redlines for back checking purposes.
03/02/2010 GARY WITTWER DOT LANDSCAPE REVIEW Approved
03/05/2010 RICHARD LEIGH PIA COORDINATOR CUSTOMER CALLED; PLANS @ AMBASSADOR Completed
03/05/2010 LANCE PETERSON DOT STREET MAINTENANCE REVIEW Approved
03/05/2010 RICHARD LEIGH PIA COORDINATOR OUT TO CUSTOMER Completed