Review Details: FLOODPLAIN

Permit Number - T10OT02336
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2010 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Floodplain and Engineering Review. Floodplain Use Permit for "Carbon-Wrap Solutions Scour wall"

11/03/2010

The project has been reviewed. The scour depth calculations are acceptable; however the floodplain use permit can not be issued until after the proposed wall is submitted for structural review and approval. Submit the wall structural plans and a geotechnical report for review. Additionally, is the original approved building lay out going to be changed considering the new proposal to build the scour wall?

Final Status

Task End Date Reviewer's Name Type of Review Description
12/22/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
12/22/2010 SUE REEVES REJECT SHELF Completed