Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T10OT01836
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/24/2010 | ELIZABETH LEIBOLD | ENGINEERING | REVIEW | Approved | September 29, 2010 FLOODPLAIN USE PERMIT # T10OT01836 PROJECT ADDRESS: 1601 W St Marys Road, Tucson AZ 85745 APPLICANT'S NAME: MPE / Swaim Assoc. PROPERTY OWNER: St Mary's Hospital & Health Center This parcel lies in a FEMA Zone A (map number 040076 C 2210K). The applicant is authorized to use a portion of the flood hazard area in the City of Tucson, Arizona, on the property described as: Parcel 116-15-088L, 1601 W St Marys Road, PTN FRAC LOTS 1 2 10 11 & 12 N2 SE4 LYG W OF SILVERBELL & S OF ST MARY'S & N OF ANKLAM 17.17 AC, in a portion of Township 14 South, Range 13 East, Section 10, for the purpose of equipment yard improvements including concrete platform/pads for hospital generator and other electrical equipment located on the north side of the main hospital structure. The applicant agrees to comply with City of Tucson Floodplain and Erosion Hazard, and Watercourse Amenities, Safety and Habitat regulations, and are particularly bound by the conditions stated below. Violation of any of the conditions stated or referred to below, as determined by the City Engineer, shall be grounds for revocation of this permit. Responsibility for renewal of this permit, if necessary, is with the applicant. Issuance of this permit does not constitute a waiver of other requirements contained in the Tucson City Code, Land Use Code, or any other Federal, State, County, or local regulation. No use other than as permitted herein is allowed. Additional uses allowed under City of Tucson Floodplain and Erosion Hazard Regulations and Watercourse Amenities, Safety, and Habitat regulations require the issuance of an additional Floodplain Use Permit. The following 12 conditions apply to permit T10OT01836: 1) Call for Pre-construction meeting, elevation certification inspections, and final inspections. For a PDSD Engineering Inspection, call IVR (740-6970), or contact PDSD Engineering at 837-4991, or schedule inspections online at: http://www.ci.tucson.az.us/dsd/Online_Services/Online_Permits/online_permits.html 2) This Floodplain Use Permit and plans shall be kept in a readily accessible location on site at all times. 3) No disturbance in Southwest Gas Corporation property on most north edge of the hospital campus. 4) Wall openings will be inspected by PDSD Engineering. 5) PDSD Engineering Inspections are required prior to final floodplain inspection. 6) Submit Elevation certification(s) by a Land Surveyor registered in Arizona for the pads for both the generator and the other electrical equipment to be installed at the west side of the enclosed equipment yard. As the RLS prefers, the 2 pad elevations may be placed on one elevation certificate. PDSD Engineering has the preliminary elevation certificate filled out for the RLS to use as needed. Assure the lowest elevation of the 2 constructed pads is provided in C2e) and E4. Notations should be added to clarify type of equipment and location. 7) All work shall conform to the approved plans for the Screen Wall at St. Mary's Medical Office Bldg. sealed on sheet xa1.1 by Mark Bollard 08/06/10. 8) Disturbance of the floodplain is only permitted as per approved construction plans. 9) Within 5 (five) days of issuance of this permit, and through completion of the project, notification must be posted and maintained in a conspicuous place on the job site stating "CONSTRUCTION PROCEEDING UNDER REQUIREMENTS OF CITY OF TUCSON FLOODPLAIN USE PERMIT # T10OT01836. FOR INFORMATION PLEASE CALL 791-5550." 10) Except as approved by the City Engineer prior to the start of construction, development under this permit shall not obstruct, retard or divert the existing flow of floodwaters from or to adjacent properties. 11) This permit becomes invalid and is subject to additional floodplain review, if any required development permit changes the configuration of the improvement, or, if there is any further disturbance within the floodplain other than that outlined in this application. This floodplain use permit may be subject to conditions or restrictions designed to reduce or mitigate the potential damage or hazard to life or property resulting from development within the regulatory floodplain, floodway or erosion hazard areas as determined by the project engineer and accepted by the City of Tucson. 12) See the associated building permit T10BU01343. This Floodplain Use Permit will be automatically revoked and becomes invalid for non-compliance to conditions set forth in this permit. Also, this permit will expire one year from its date of issue. Renewal of this permit will require a new application, review and approval of that application by the City of Tucson, Planning & Development Services Department, Engineering Division. (EXPIRATION DATE) Month: 9 Day: 29 Year: 2011 APPLICANT: MPE / Swaim Assoc ADDRESS: 7650 E Speedway Bl #210, Tucson, AZ 85710 PHONE: (520) 326-6700 (Contact Person: Mark Bollard, R.A.) OWNER: Carondelet Health Network / St Mary's Hospital & Health Center |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/15/2010 | DELMA ROBEY | OUT TO CUSTOMER | Completed |