Permit Number: T10OT01793
Parcel: 10706069B

Address:
930 W GLENN ST

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T10OT01793
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/10/2010 LOREN MAKUS ENGINEERING REVIEW Denied September 13, 2010
T10BU01330
T10OT01793
Grading and Floodplain review.

1. The Developed Flood Limit Line must be shown on the grading plan.
2. The label for the water harvesting basin references a detail on Sheet 4. Please revise.
3. Clearly label the areas to be over-excavated in accordance with the Geotechnical Engineering Report.
4. Provide general dimensions on the grading plan for all features such as parking spaces, the solid waste enclosure, curb radii, sidewalks and buildings.
5. Provide bollards or other means to prevent vehicles from driving into the unpaved areas of the site.
6. Clearly label and dimension the loading zones.
7. Provide labels and dimensions for landscape/planting islands.
8. There are two callouts for section B/3. The two areas are not similar enough to be represented by the same detail. Please provide additional details and callouts as necessary.
9. The SWPPP and floodplain use permit will be approved with the grading plan.

Loren Makus, EIT
Loren.makus@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/28/2010 CINDY AGUILAR OUT TO CUSTOMER Completed
12/28/2010 SUE REEVES REJECT SHELF Completed