Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - SITE ALL
Permit Number - T10OT00728
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/02/2010 | STEVE SHIELDS | ZONING | REVIEW | Denied | PDSD TRANSMITTAL FROM: Steve Shields Lead Planner PROJECT: Freeway Industrial Loop Lot 1 T10CM00728 Site Plan (2nd Review) TRANSMITTAL DATE: June 2, 2010 COMMENTS: Please resubmit revised drawings and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed. 1. This site plan was reviewed for compliance with the City of Tucson Development Standards (D.S.) and Land Use Code (LUC). This project has been reviewed for full code compliance for the entire site. 2. This comment was not addressed. Per a discussion with David Rivera this project is an expansion of vehicle parking for the existing Long property to the north. Provide a copy of a recorded Covenant Regarding Development and Use of Real Property prior to approval of the site plan. 3. There are two uses listed in LUC Section 3.3.4 under the RECREATION USE GROUP that have a vehicle parking space ratio of 1space per 200 sq. ft. of gross floor area, Billiard/Pool Halls & Skating Rink, Billiard/Pool Halls bicycle parking is 8% and Skating Rink is 15% Clarify which use is proposed so that the required bicycle parking can be verified. The last approved plan showed the percent for bicycle parking at 15%. That said additional bicycle parking may be required. 4. D.S. 2-02.2.2.A.4 Based on the last approved plan D1-A There were 79 vehicle parking spaces provided minus 1 for the planter area plus 44 new vehicle parking spaces = 122 provided on site. The calculation shown on sheet 1 of 4 shows 118 standard and 7 handicapped for a total of 125. Clarify the total number of provided vehicle parking spaces provided. 5. This comment was not addressed. D.S. 2-02.2.2.A.5 Percentage of vehicle use area and or lot area expansion. If the building(s) or lot area have been previously expanded, those calculations shall be included. Provide a cumulatively vehicle use area expansion calculation and a lot area expansion calculation, see comment 4 above. 6. Depending on how the above comments are addressed addition comments may be forth coming. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956. C:\planning\site\t10cm00728 RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and additional requested documents. |
| 06/03/2010 | RONALD BROWN | ZONING HC | REVIEW | Denied | 1. Please provide a painted (marked) crossing at the entrance drive. 2. Of the two accessible parking spaces provided, one must be "Van Accessible" with a parking space width of 8' and an aisle of 8' or 11' parking and 5' aisle. Please revise detail numbers 1/2 and C/4. 3. At the North East marked crossing: a. Please provide a detectable warning at the South West termination point in the concrete landing. b. Please show the North East termination point including all required ramps, detectable warning strips, dimenmsions and slopes as per section 406.12, 406.14 and 403.3. END OF REVIEW |
| 06/03/2010 | ANDREW CONNOR | LANDSCAPE | REVIEW | Approved | |
| 06/07/2010 | JASON GREEN | ENGINEERING | REVIEW | Denied | DATE: June 7, 2010 SUBJECT: 3260 N Freeway Industrial Loop Site Plan- 2nd Engineering Review TO: A23 Studios Attn: Jose Ceja LOCATION: T13S R13E Sec27 Ward 1 REVIEWERS: Jason Green, CFM ACTIVITY: T10OT00728 (Site Plan) SUMMARY: Engineering Division of Planning & Development Services Department has received and reviewed the revised Site Plan (T10OT00728) and Drainage Statement (David G Laredo, PE, 30MAR10) for the above referenced property. Engineering Division does not recommend approval of the Site Plan application at this time. The following items need to be addressed: SITE PLAN COMMENTS: 1) Complied. 2) Acknowledged. 3) Restated: DS Sec.2-02.2.1.A.8: Label and dimension the minimum intersection radii for the PAAL entrance point. Per DS Sec.3-05.2.1.3 when PAALs are designated as fire lanes or are used as access lanes for refuse collection or loading zones, a minimum unobstructed radius of eighteen (18) feet is required where they intersect another PAAL. A minimum unobstructed radius of five (5) feet is required, clarify. Include radii at all landscape islands and curb radii. 4) Complied. 5) Complied. 6) Be advised that further comments may be forth coming on resubmittal of the Site Plan. GRADING PLAN: 7) DS Sec.11-01.2.1: A grading permit application is required for this project due to the proposed cut and fill quantities. It is acknowledged that the plan set has been submitted as a Site/Grading Plan however the grading permit application must still be provided for stamped approval. 8) Please ensure that any future grading plan will be consistent with the site plan and Drainage Statement. Grading standards may be accessed at: http://www.ci.tucson.az.us/dsd/DevStandsTOC.pdf GENERAL COMMENTS: Please provide a revised Site Plan that addresses the comments provided above. Include a comprehensive response letter and any supplemental information addressing in detail responses to all of the above comments. Enclose "redlines" with the resubmittal package. Further comments may be generated upon resubmittal of the Site Plan review. For questions or to schedule an appointment I can be reached at 837-4929. Jason Green, CFM Senior Engineer Associate Engineering Division Planning & Development Services Department |