Permit Number: T10EL02663
Parcel: 12809016D

Address:
4701 E 22ND ST

Review Status: Completed

Review Details: BILLBOARD - BLDG/ELEC30days

Permit Number - T10EL02663
Review Name: BILLBOARD - BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
11/30/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
12/23/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the electrical repair submittal for COT ID# 80 at
4701 East 22nd Street (T10EL02663).

Sheet 1 of 4

No comments.

Sheet 2 of 4

No comments.

Sheet 3 of 4

1. In the Partial Plan View, conform the number of conductors in the
wiring run between the two faces to the single ciruit being served; where
indicated, clarify the need for four conductors between the panel and the
first junction box or that no more than two conductors will serve each of
the two lighting circuits.

2. In upper Note #2 add unless noted otherwise.

3. Provide the manufacturer's literature and photograph (with cover open
and showing interior breaker cover plate) for the replacement panel (may
alternatively be provided on Sheet 4).

4. Indicate the manufacturer and model number of the time control unit.

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/04/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/04/2011 SUE REEVES REJECT SHELF Completed