Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10EL02662
Parcel: 99999999B

Address:
2112 E BENSON HY

Review Status: Completed

Review Details: BILLBOARD - BLDG/ELEC30days

Permit Number - T10EL02662
Review Name: BILLBOARD - BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2011 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
01/19/2011 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
02/03/2011 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the electrical repair resubmittal for COT ID# 8 at
2112 East Benson Highway (T10EL02662).

Sheet 2 of 2

1. The original comment #1 (12/22/10) indicated that the loads shown in the
Panel Schedule for the two lighting circuits (using two VHO lamps each) were
understated and needed to be corrected. Those loads shown were 800 v-a
whereas the actual loads for each lighting circuit are approximately 860 v-a
(two Universal WPR-931 ballasts@ input power of 431 watts each for each
circuit; the ballasts used are as per Sheet 3 of the approved plans for
T10EL00835). The panel schedule resubmitted here, however, now shows 1650
v-a per lighting circuit, far in excess of the actual loads and any normal
cushion. Either the panel schedule needs to be corrected or a notation
needs to be added making reference to the approved plans for T10EL00835 and
that the devices on the lighting circuits are limited to those shown on the
T10EL00835 approved plans.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/11/2011 DELMA ROBEY OUT TO CUSTOMER Completed
02/11/2011 SUE REEVES REJECT SHELF Completed