Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T10EL02662
Parcel: 99999999B

Address:
2112 E BENSON HY

Review Status: Completed

Review Details: BILLBOARD - BLDG/ELEC30days

Permit Number - T10EL02662
Review Name: BILLBOARD - BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
11/30/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
12/23/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Denied BRC Comments

Below are comments for the electrical repair submittal for COT ID# 8 at 2112
East Benson Highway (T10EL02662).

Sheet 2 of 2

1. The loads shown in the Panel Schedule for the two lighting circuits
(using two VHO lamps each) are understated and need to be corrected.

2. Resolve inconsistency between the Notes that indicate 122 existing and
replacement panels (30A) and the 206 existing replacement panels (60A) shown
otherwise; if the replacement panel is to be a 122, the panel schedule needs
to show the time control on one of the two lighting circuits and the
remaining entry spaces need to be deleted or crossed out.

3. Provide the manufacturer's literature and photograph (with cover open
and showing interior breaker cover plate) for the replacement panel.

4. Indicate the manufacturer and model number of the time control unit.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/11/2011 CPIERCE1 OUT TO CUSTOMER Completed
01/11/2011 SUE REEVES REJECT SHELF Completed