Permit Number: T10EL02573
Parcel: 135074450

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T10EL02573
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/10/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10EL02573
1603 S Pantano #205


1. Feeder from WPJB to panel is a 100 amp feeder, at the J -Box another feeder is taken sized at 3/0, should be a
#10 ? Also will this feeder comply with the tap rule ?
2. Circuit DPB1-20,22,24 shows as circuits 22,24,26 in plan.
3. Show a ground for the 45KVA transformer and size.
4. Heat Exchanger shows circuit DPB1 11,13,15, should beas in panel 13,15,17.
5. Provide a discription of process this equipment will preform and include any type of chemicals used in process, trying to see if any hazardous materials used in process.


Ray T Majuta,
PDSD, City of Tucson,
Elect PLan CK,
11/10/10,
520-837-4988