Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T10EL02573
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/10/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10EL02573 1603 S Pantano #205 1. Feeder from WPJB to panel is a 100 amp feeder, at the J -Box another feeder is taken sized at 3/0, should be a #10 ? Also will this feeder comply with the tap rule ? 2. Circuit DPB1-20,22,24 shows as circuits 22,24,26 in plan. 3. Show a ground for the 45KVA transformer and size. 4. Heat Exchanger shows circuit DPB1 11,13,15, should beas in panel 13,15,17. 5. Provide a discription of process this equipment will preform and include any type of chemicals used in process, trying to see if any hazardous materials used in process. Ray T Majuta, PDSD, City of Tucson, Elect PLan CK, 11/10/10, 520-837-4988 |