Permit Number: T10EL02387
Parcel: 118121770

Address:
544 E 24TH ST

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T10EL02387
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project:T10EL02783
544 E 24th ST
New Service 1200 A 277/480v

The new service is required to be grouped with the existing per 2005 NEC 230.72.

Ray T Majuta
PDSD, City of Tucson
10/22/10