Permit Number: T10EL02266
Parcel: 115050030

Address:
150 E GRANT RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL02266
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/05/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/27/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/28/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Below are comments for the lighting modification & electrical repair
submittal for COT ID# 444 at 150 East Grant Road (T10EL02266).

Sheet 1 of 8

No comments.

Sheet 2 of 8

1. Add removal and reinstallation of wood sections in scope of work
(specify which sections); add detail for wood sections, Z clips and any
other parts to be removed and installed.

2. Provide detail on the existing stringer supports that the upper light
mounting assembly is to replace (including gauge); provide length of the
replacement stringer supports (shown as 4x4x5/16).

Sheet 3 of 8

1. Clarify if wood sections are to be removed and reinstalled on the north
end of the west face as well as the south end.

2. Clarify the apparent inconsistency between the Notes and the Elevation
as to number of junction boxes ((2) vs. (3)) and the position of the
horizontal conduit between the two upper junction boxes (upper or lower);
clarify the need for a third junction box with this configuration; it also
appears that the single horizontal conduit run powering both faces would
need (3) conductors rather than (2).

Sheet 4 of 7

No comments.

Sheet 5 of 7

1. Add notation that photometric data is continuation of that shown on
Sheet 4 for IES File 103328_L.

Sheet 6 of 7

No comments.

Sheet 7 of 7

1. Add notation that photometric data is continuation of that shown on
Sheet 6 for IES File 103328_R.

Sheet 8 of 8

No comments.