Permit Number: T10EL02182
Parcel: 99999999B

Address:
827 W GRANT RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL02182
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/21/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/22/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Below are comments for the lighting modification & electrical repair
submittal for COT ID# 451 at 837 West Grant Road (T10EL02182).

Sheet 1 of 8

No comments.

Sheet 2 of 8

1. The engineer's stamp needs to be dated.

Sheet 3 of 8

1. Reduce the number of circuits to one (1) per face and adjust the number
of conductors and breakers accordingly.

2. Add unless noted otherwise to Note #2 on THHN conductors.

3. The volt-amp entries do not match the luminaire/ballast load; correct in
conjunction with circuit adjustment.

4. Resolve inconsistency between Panel Schedule and New Electrical Riser
Diagram on panel rating (100A vs. 60 A).

5. Resolve inconsistency where Elevation shows conduit/wiring from panel to
junction box at north end of billboard and Partial Plan View shows
connection at south end; also correct or delete second branch note on
Elevation.

6. Add Stipulation address.

Sheet 4 of 7

1. Add Stipulation address.

Sheet 5 of 7

1. Add notation that photometric data is continuation of that shown on
Sheet 4 for IES File 103328_L.

2. Add Stipulation address.

Sheet 6 of 7

1. Add Stipulation address.

Sheet 7 of 7

1. Add notation that photometric data is continuation of that shown on
Sheet 6 for IES File 103328_R.

2. Add Stipulation address.

Sheet 8 of 8

1. Add Stipulation address.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2010 SUE REEVES APPROVAL SHELF Completed
10/22/2010 CPIERCE1 OUT TO CUSTOMER Completed