Permit Number: T10EL02180
Parcel: 99999999B

Address:
4947 N ORACLE RD

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL02180
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/21/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/21/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/22/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Below are comments for the lighting modification & electrical repair
submittal for COT ID# 483 at 4947 North Oracle Road (T10EL02180).

Sheet 1 of 8

No comments.

Sheet 2 of 8

1. The engineer's stamp needs to be dated.

2. Add detail on wood sections, Z clips and any other parts to be removed
and reinstalled.

Sheet 3 of 8

1. Reduce the number of circuits to one (1) per face and adjust the number
of conductors and breakers accordingly.

2. Add unless noted otherwise to Note #2 on THWN/THHN conductors.

3. Clarify if existing wood section panels are to be replaced or
reinstalled (if replaced, Sheet 2 needs to be corrected)

4. Resolve inconsistency between Panel Schedule and Existing One-Line
Diagram on panel rating (100A vs. 60 A).

Sheet 4 of 7

No comments.

Sheet 5 of 7

1. Add notation that photometric data is continuation of that shown on
Sheet 4 for IES File 103328_L.

Sheet 6 of 7

No comments.

Sheet 7 of 7

1. Add notation that photometric data is continuation of that shown on
Sheet 6 for IES File 103328_R.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2010 SUE REEVES APPROVAL SHELF Completed
10/22/2010 CPIERCE1 OUT TO CUSTOMER Completed