Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T10EL02152
Parcel: 99999999B

Address:
2200 N FREEWAY

Review Status: Completed

Review Details: BILLBOARD-BLDG/ELEC30days

Permit Number - T10EL02152
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/21/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
10/22/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond BRC Comments

Below are comments for the lighting modification & electrical repair
submittal for COT ID# 535 at 2200 North Freeway (T10EL02152).

Sheet 1 of 4

No comments.

Sheet 2 of 4

No comments.

Sheet 3 of 4

1. Reduce the number of circuits to one (1) per face and adjust the number
of conductors and breakers accordingly.

2. Add unless noted otherwise to Note #2 on THHN conductors.

Sheet 4 of 4

No comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/22/2010 SUE REEVES APPROVAL SHELF Completed
10/22/2010 CPIERCE1 OUT TO CUSTOMER Completed