Permit Review Detail
Review Status: Completed
Review Details: BILLBOARD-BLDG/ELEC30days
Permit Number - T10EL02152
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2010 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/21/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/22/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Approv-Cond | BRC Comments Below are comments for the lighting modification & electrical repair submittal for COT ID# 535 at 2200 North Freeway (T10EL02152). Sheet 1 of 4 No comments. Sheet 2 of 4 No comments. Sheet 3 of 4 1. Reduce the number of circuits to one (1) per face and adjust the number of conductors and breakers accordingly. 2. Add unless noted otherwise to Note #2 on THHN conductors. Sheet 4 of 4 No comments. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/22/2010 | SUE REEVES | APPROVAL SHELF | Completed |
| 10/22/2010 | CPIERCE1 | OUT TO CUSTOMER | Completed |