Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T10EL02103
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/09/2010 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | Project: T10EL2103 Electrical plans denied for following: 1. Provide cut sheets for the Fire Pump and Fire Pump Controller. 2. Correct the Over-current selection at Main for feeder to Fire Pump. 3. Indicate that the Disconnect Means for the Fire Pump to be marked per 2005 NEC 695-B.3 4. Provide the type of conduit systems to be used for new conductors as per 2005 NEC 695 5.Please be aware that even tho the existing installation was installed under the 2002 NFPA-, the equipment installed as new or replaced will be under the current NFPA20-2007. please indicate this on electrical sheet.The current NEC 695 to be complied with also. Ray T Majuta Elect Pln CK PDSD, City of Tuc, 9/9/10 520-837-4988 520-909-4891 |