Review Date Reviewer's Name Type of Review Description Status Comments
09/09/2010 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied Project: T10EL2103

Electrical plans denied for following:

1. Provide cut sheets for the Fire Pump and Fire Pump Controller.
2. Correct the Over-current selection at Main for feeder to Fire Pump.
3. Indicate that the Disconnect Means for the Fire Pump to be marked per 2005 NEC 695-B.3
4. Provide the type of conduit systems to be used for new conductors as per 2005 NEC 695
5.Please be aware that even tho the existing installation was installed under the 2002 NFPA-, the equipment installed as new or replaced will be under the current NFPA20-2007.
please indicate this on electrical sheet.The current NEC 695 to be complied with also.



Ray T Majuta
Elect Pln CK
PDSD, City of Tuc,
9/9/10
520-837-4988
520-909-4891