Review Date Reviewer's Name Type of Review Description Status Comments
09/20/2010 LEERAY HANLY BUILDING-COMMERCIAL REVIEW Approved
10/08/2010 GLENN MOYER ADMINISTRATIVE ADMIN REVIEW Approv-Cond Below are comments for the lighting modification & electrical repair
submittal for COT ID# 364 at 4411 East Speedway Boulevard (T10EL02099).

Sheet 1 of 8

No comments.

Sheet 2 of 8

No comments.

Sheet 3 of 8

1. Reduce the number of circuits to one (1) per face and adjust the number of conductors and breakers accordingly.

2. Add unless noted otherwise to Note #2 on THHN conductors.

Sheet 4 of 7

No comments.

Sheet 5 of 7

1. Add notation that photometric data is continuation of that shown on
Sheet 4 for IES File 103328_L.

Sheet 6 of 7

No comments.

Sheet 7 of 7

1. Add notation that photometric data is continuation of that shown on
Sheet 6 for IES File 103328_R.
10/08/2010 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
10/08/2010 SUE REEVES APPROVAL SHELF RECEIVED