Permit Number - T10EL02098
Review Name: BILLBOARD-BLDG/ELEC30days
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 09/20/2010 | LEERAY HANLY | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/08/2010 | GLENN MOYER | ADMINISTRATIVE | ADMIN REVIEW | Approv-Cond | Below are comments for the lighting modification & electrical repair submittal for COT ID# 56 at 430 West 22nd Street (T10EL02098). Sheet 1 of 8 No comments. Sheet 2 of 8 No comments. Sheet 3 of 8 1. Reduce the number of circuits to one (1) per face and adjust the number of conductors and breakers accordingly. 2. Add unless noted otherwise to Note #2 THHN conductors. 3. Panel Schedule & New One-Line Diagram: resolve the inconsistency on the panel ratings (100A vs. 60A). Sheet 4 of 7 No comments. Sheet 5 of 7 1. Add notation that photometric data is continuation of that shown on Sheet 4 for IES File 103328_L. Sheet 6 of 7 No comments. Sheet 7 of 7 1. Add notation that photometric data is continuation of that shown on Sheet 6 for IES File 103328_R. |
| 10/08/2010 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved |